Horner APG QX651 OCS User Manual

Page 6

Advertising
background image

MAN0797-03-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________
9/16/2009 Page 6 of 7 ECN # 968















Figure 10 – QX Back Pack Connectors and Ports (Side Views)























Figure 11 – QX Back Pack I/O Port







4

Safety














Table 1 – I/O Port Pins (HSC) (Orange Connector)

Pin

Signal

Description

1

TTL In1

HSC 1 / 5 V Input 1 (See Note*)

2

TTL In2

HSC 2 / 5 V Input 2 (See Note*)

3

TTL In3

HSC 3 / 5 V Input 3 (See Note*)

4

TTL Out1

HSC 1 / 5 V Output 1 (See Note*)

5

TTL Out2

HSC 2 / 5 V Output 2 (See Note*)

6

0 V

Ground

(For best performance, use separate supply and

isolated ground.)

7

In1

HSC 1 / 24 V Input 1 (See Note*)

8

In2

HSC 2 / 24 V Input 2 (See Note*)

9

In3

HSC 3 / 24 V Input 3 (See Note*)

10

Out1

HSC 1/ 24V Output 1 / PWM 1

11

Out2

HSC 2/ 24V Output 2 / PWM 2

12

+24 V

Power for Outputs

Note* - Depending on the output of the application, use

5 V (e.g., TTL In1) or 24 V (e.g., In1) per channel.

001BP003

I/O PORT

O

U

T

2

O

U

T

1

IN

3

IN

2

IN

1

O

U

T

2

O

U

T

1

TTL

IN

3

IN

2

IN

1

E

X

T

0

V

E

X

T

+

2

4

V

Close-up of the Back Pack I/O Connector

PI

PI2

P 12

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-hazardous locations only

WARNING – EXPLOSION HAZARD
– Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
AVERTISSEMENT - RISQUE D'EXPLOSION - AVANT DE DECONNECTOR L'EQUIPMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST
DESIGNE NON DANGEREUX.

WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth) ground before making any other connections.

WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close
to the source as possible.

WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards.

WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse.

3.5

CAN Network Port and Wiring (QX Base and QX Back Pack)


See the latest edition of Horner’s CAN Networks Manual (MAN0799) by referring to the website location listed in the Technical Support section in this document.

Note:
To optimize CAN network reliability in electrically noisy environments, the V- CAN Ground needs to be isolated from the primary input power supply ground.

Warning: Consult
user documentation.

Warning: Electric
Shock hazard

When found on the product, the following symbols specify: