Conversion of Real-World Inputs into Register Values

Selected Range

Input

mA or Volts

Data Out

Conversion Factor

> +5.11

32767

+5.00

32000

0.00

0

-5.00

-32000

±5.00 V

< -5.11

-32768

0.00015625

> +10.23

32767

+10.00

32000

0.00

0

-10.00

-32000

±10.00 V

< -10.23

-32768

0.0003125

< +20.37

32767

+20.00

32000

+4.00

0

-12.00

-32000

4.20 mA

> -12.38

-32768

0.0005

> +20.47

32767

+20.00

32000

0

0

-20.00

-32000

±20.00 mA

< -20.47

-32768

0.0006250

Note: For the 4 to 20mA range, the offset, 4mA, must first be subtracted from the physical input value

before dividing by the scale factor to yield the expected %AQG value for the given input.



7

SETTING ID SWITCHES


CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The decimal
equivalent is 1-253. Refer to following Conversion Table, which shows the decimal equivalent of
hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver into the two
identical switches.

Note:
The CsCAN Baud Rate for SmartStix I/O is fixed at 125KBaud













Close-up of Switches

LO (x1)

HI (x16)

MS

NS

P W R

SmartStix I/O

006DIQ001

Use this switch to set
the Low Digit – has an
x1 multiplier.

Use this switch to set the
High Digit –has an x16
multiplier.

Power and Diagnostic

LEDs