PRotectionS

overload and short circuit on the Ac output side

- If the load exceeds 120W, the output voltage will start dropping, but the unit will

NoT shut down.

- The LeD Status Indicator (2, fig. 2.1) will remain GreeN.

-

The output voltage waveform will be distorted and will not have pure sine waveform,
but will be clipped at top and bottom and will look like a square waveform.

- There will be excessive rf noise.

- The until will reset automatically once the overload/short circuit is removed.

over temperature due to fan failure or due to lack of cool replacement air

- The unit will shut down if temperature of hot spot inside the unit > 105°C. The LeD

Status Indicator (2, fig. 2.1) will turn orANGe.

- The unit will reset automatically on cooling.

Low Dc input Voltage

- The unit will shut down if DC input voltage is < 10 VDC.

- The LeD Status Indicator (2, fig. 2.1) will turn orANGe.

- The unit will reset automatically when the voltage rises to 11.5 VDC.

High Dc input Voltage

- The unit will shut down if DC input voltage > 16.5 VDC.

- The LeD Status Indicator (2, fig. 2.1) turns orANGe.

- The unit will reset automatically when voltage is < 16.5 VDC.

over Voltage on USB Port

- USb output is shut down if USb output ≥ 6.2 VDC.

- The LeD Status Indicator (2, fig. 2.1) will be off or reD.

operational conditions indicated by the LeD Status Indicator (2, fig. 2.1) are given in
the following table: