CPI PDU User Manual Rev. 10.0.

June 28, 2010

17

PDU MAC Address: Contains the assigned MAC address for the PDU’s network
interface hardware. This value cannot be changed.

Subnet Mask: Contains the network masking bits for the PDU in the form of
xxx.xxx.xxx.xxx, where xxx is usually 255 or 0 to designate a bit pattern that masks
in the network address portion of the IP address. These values depend on the
network class of the assigned IP address.

Gateway: Contains the IP address of the network’s gateway PDU in the form of
xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254.

AutoIP Checkbox: Check to use a dynamic IP address assigned by a DHCP server
instead of the static IP assigned in the PDU IP Address field. A static IP address is
required with SEMA to log current, temperature and humidity readings.

Hosts Checkbox: Check to indicate that only the Hosts identified in the SNMP Hosts
IP Address fields can access the PDU via SNMP. When unchecked, any host can
access the PDU via SNMP.

WEB Checkbox: Check to allow access to the PDU using a web browser. This box
should always be checked.

SWU Checkbox: Check to allow software updates.

SNMP Host1 IP Address: The PDU will send current, temperature and humidity
alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not required
when SEMA is used to monitor the PDU.

SNMP Host2 IP Address: The PDU will send current, temperature and humidity
alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not required
when SEMA is used to monitor the PDU.

SNMP Host3 IP Address: The PDU will send current, temperature and humidity
alarms to this IP Address as SNMP traps. Leave 0.0.0.0 to disable. Not required
when SEMA is used to monitor the PDU.

PDU Name: Name assigned to this PDU, the maximum number of characters that
can be entered is less than 32.

PDU Password: Holds the password used by the PDU to access SEMA. This is a
protected variable accessible only by SEMA. This field is only required when using
the PDU with SEMA.

SEMA Name: Name of the SEMA group that this PDU belongs to. This is a
protected variable accessible only by SEMA. This field is only required when using
the PDU with SEMA.

SEMA Password: Holds the password used by SEMA to access this PDU. This is a
protected variable accessible only by SEMA. This field is only required when using
the PDU with SEMA.