Campbell Scientific RavenXTV CDMA Sierra Wireless Cellular Modem User Manual

Page 30

Advertising
background image

Appendix A. AceManager Setup without Template File

• S23 — Configure Serial Port — The baud rate needs to be configured to

match a valid datalogger baud rate. For a CR10X: 9600,8N1 and for a
CR1000: 115200,8N1.

• \Q — Serial Port Flow Control — This should be set to None.

• V — AT Verbose Mode — Set this to Verbose for CR800, CR1000,

CR3000; Numeric for CR10(X), CR510, CR23X.

• &D — DTR Mode — Set to Ignore DTR

• S211 — DTR Mode – Set to Ignore DTR

• S0 — TCP Auto Answer — Set to On

• TCPT — TCP Idle Timeout — Set to a reasonable value like 2 min.

A-2