5: If (X<=>F) (P89)

if the heater is on (heater

1: 10

-- X Loc [ Heat_1 ]

control location <>0)

2: 2

<>

3: 0

F

4: 30

Then

Do

then


6: If (X<=>F) (P89)

check upper threshold

1: 1

-- X Loc [ Temp_1 ]

to see if heater should

2: 3

>=

be turned off

3: 25.5

F

4: 30

Then

Do


7: Z=F (P30)

if heater should be turned

1: 0

F

off, enter a ‘0’ into

2: 0

Exponent

of

10

heater control location

3: 10

-- Z Loc [ Heat_1 ]


8: End (P95)

end ‘then do’


9: Else (P94)

else, if the heater is off


10: Z=F (P30)

enter a ‘0’ into heater

1: 0

F

control location

2: 0

Exponent

of

10

3: 10

-- Z Loc [ Heat_1 ]


11: End (P95)

end ‘then do/else’


End heater control logic

Start cooler control logic

12: If (X<=>F) (P89)

if ‘cooler on’ threshold

1: 1

-- X Loc [ Temp_1 ]

is exceeded

2: 3

>=

3: 27.5

F

4: 30

Then

Do

then


13: Z=F (P30)

put a ‘1’ into cooler

1: 1

F

control location

2: 0

Exponent

of

10

3: 15

-- Z Loc [ Cool_1 ]


14: End (P95)

end ‘then do’


15: If (X<=>F) (P89)

if cooler is on (cooler

1: 15

-- X Loc [ Cool_1 ]

control location <>0)

2: 2

<>

3: 0

F

4: 30

Then

Do

then

11