2. Control Specifications

2.1 General

Compatible dataloggers:

CR800, CR850, CR1000, CR3000, CR5000,
CR10(X), CR23X, CR7 and 21X

Operating voltage:

12 VDC nominal (9 to 18 V)

Current drain at 12V DC: 100 µA typical (All ports HI, no load)

Total cable length:

6 m (CR10/10X, CR23X, 21X), 180 m (CR7)

2.2 Output Specifications

Output Voltage (no load): Output ON/HI, Nominal 5 V (Minimum 4.5 V)

Output OFF/LO, Nominal 0 V (Maximum 0.1 V)

Output Sink Current:

Output will sink 8.6 mA from a 5 V source*

Output Source Current:

Output will source 36 mA @ 3 V,

115 mA short-circuited to ground*

Max. Output Current:

400 mA at 50°C and 12 V supply (see NOTE below)

(total all outputs)

The maximum current should be derated under the following
conditions: 50 mA for every 10°C above 50°C and/or 50 mA for
every volt above 12 V.

NOTE

Operating temp.:

-25°C to +70°C standard

Size:

230 mm wide x 100 mm high x 24 mm deep

Weight: 350

g

EMC Status:

Complies with EN55022-1:1998 and
EN50082-1:1998

* If more detailed output characteristics are required, experienced users should
consult the equivalent circuit diagrams shown in Figure 2, below.

0.6V Drop

Output

Output

580R

Output set ON/HI

Output set OFF/LO

510R

39R

V

5V, 0

FIGURE 2. Equivalent Output Driver Circuit

2