1 wiring, 1 sdm-cd16s power and control connections – Campbell Scientific SDM-CD16S 16-Channel Solid State DC Relay Controller Module User Manual

Page 9

Advertising
background image

SDM-CD16S 16 Channel Solid State DC Control Module

For datalogger connections, see Table 1.

Multiple SDM-CD16Ss may be wired in parallel by connecting the datalogger
side of one SDM-CD16S to the next. In most installations the total length of
the cables connecting the SDM-CD16S and other SDM peripherals should not
exceed 20 feet.

Total cable lengths in excess of 20 feet may adversely influence
communication performance. (For CR7 dataloggers, the total cable length
should not exceed 600 feet.)

4.1 Wiring

4.1.1 SDM-CD16S Power and Control Connections

Refer to Figure 3 and Table 1 for SDM-CD16S operating power and control
connections to the datalogger.

EXTERNAL

7 TO 48 VDC

+ —

SDM-CD16S

DATALOGGER

GND

C1
C2
C3

Connection to External Supply


SDM-CD16S

DATALOGGER

12 V
C1
C2
C3

GND

Connection to Datalogger Supply

FIGURE 3. Connection Block Diagrams

5