Campbell Scientific SDM-CD8S 8 Channel Solid State DC Control Module User Manual

Page 19

Advertising
background image

SDM-CD8S 8 Channel Solid State DC Control Module


10: Z=F (P30)

1: 0

F

Enter a "0" into heater

2: 0

Exponent of 10

control location

3: 11--

Z Loc :


11: End (P95)

End Then Do/Else/End


END HEATER CONTROL LOGIC

START COOLER CONTROL LOGIC

12: If X<=>F (P89)

If "Cooler" on

1: 1--

X

Loc

threshold is

2: 3

>=

exceeded

3: 27.5

F

4: 30

Then

Do

Then


13: Z=F (P30)

Put a "1" into cooler

1: 1

F

Control Location

2: 0

Exponent of 10

3: 13--

Z Loc :


14: End (P95)

End Then Do/End


15: If X<=>F (P89)

If cooler is on

1: 13--

X

Loc

(Cooler control

2: 2

<>

Location <>0)

3: 0

F

4: 30

Then

Do

Then


16: If X<=>F (P89)

Check lower threshold to

1: 1--

X

Loc

see if cooler should be

2: 4

<

turned off

3: 24.5

F

4: 30

Then

Do


17: Z=F (P30)

If cooler should be turned

1: 0

F

off, put a "0" into cooler

2: 0

Exponent of 10

control location

3: 13--

Z Loc :


18: End (P95)

End Then Do/End


19: Else (P94)

Else if cooler is off


20: Z=F (P30)

1: 0

F

Put a "0" into cooler

2: 0

Exponent of 10

control location

3: 13--

Z Loc :


21: End (P95)

End Then Do/Else/End


END COOLER CONTROL LOGIC

13