step 6. Set
NEG FIELD MAX
at or below the
FIELD MAX
setting.
If the controller is tuned such that the system is operating
outside the motor’s safe commutation region, there will be au-
dible and visual indications. Under normal operation, the mo-
tor will emit a whine with a pitch that increases with increasing
rotation speed. If a “scratchy” sound is also heard, this is usually
an indication that pin arcing is occurring in the motor and it is
operating outside its safe commutation region. This operation is
normally accompanied by a strong smell from the motor. If the
brushes and commutator bars are visible, arcing may be visible.
The further outside the safe commutation region the motor is
operating, the worse the arcing will be. Operation outside the
safe commutation region is very detrimental to the motor.
The
FIELD MIN
and possibly also the
FIELD RAMP
should be increased
until the indications of arcing stop. Decreasing
FIELD MAP START
will also help to move operation back into the safe commutation
region.
The typical default field map settings are as follows.
5 — TUNING GUIDE
Further tuning of the field maps is described in procedures 5,
7
, and 9.
- BC-6200-8CA BC-6000-8SA BC-6000-8CA BC-6200-8SAC BC-6250-8SA BC-6250-8CA BC-620-8SA BC-620-8CA BC-600-8SA BC-600-8CA BC-625-8SA BC-625-8CA SCT-7750-8AC SCT-7750-8SA SCT-7750-8CA SCT-7750-6AC SCT-7750-8AC-MTR SCT-7750-8CA-MTR PC-325-6SA PC-325-6CA PMT-5000-8CA PMT-5000-8SA PMT-4500-8SA PMT-4500-8CA SC-775-8CA SC-775-8SA SC-775-8AC