ATS/Voltage

36

InfraStruXure Power Generation System

ATS Blocking

• Transfer Blocking: Defines conditions that will prevent the ATS from transferring

from Source 1 to Source 2. The following is displayed on the Transfer Blocking screen:

– Block Transfer: Lists configured input contacts that will prevent a transfer from

occurring.

– Map: Choose from the following input contacts to block a transfer:

C1: Contact 1
C2: Contact 2
C3: Contact 3
C4: Contact 4

– Apply Now: After you have made changes on this screen, choose this option and

press

E

NTER

to save your changes.

• Retransfer Blocking: Defines conditions that will prevent the ATS from transferring

from Source 2 to Source 1. The following is displayed on the Retransfer Blocking
screen:

– Block Retransfer: Lists configured input contacts that will prevent a retransfer from

occurring.
Map: Choose from the following input contacts to block a retransfer:
C1: Contact 1
C2: Contact 2
C3: Contact 3
C4: Contact 4

– Apply Now: After you have made changes on this screen, choose this option and

press

E

NTER

to save your changes.

• Gen Start Blocking: Defines input contacts that will prevent the generator from

starting because of a line failure:

– Block Gen Start: Lists configured input contacts that will prevent the generator from

starting.

– Map: Choose from the following input contacts to block the generator from starting:

C1: Contact 1
C2: Contact 2
C3: Contact 3
C4: Contact 4

– Apply Now: After you have made changes on this screen, choose this option and

press

E

NTER

to save your changes.

Other Settings

• S1 Name: Create a unique name for Source 1 (maximum of 9 characters). The default

is Utility.

• S2 Name: Create a unique name for Source 2 (maximum of 9 characters). The default

is Generator.

• Preferred: Displays the preferred source (Source 1).

Advertising