Appendix: Custom Installations

If Source 2 is a Second Utility

Differences in your system from information presented in this manual

The ATS was designed for operation with an APC InfraStruXure generator, and this manual assumes

that Source 2 is an APC InfraStruXure generator. If using a secondary utility instead of a generator,

almost all references to the “generator” should be considered references to your second utility as

well. However, the following sections will not apply to your system and should be disregarded:

• “Generator start sequence” on page 7

• “Generator cool-down” on page 7

• “Fuel monitoring/runtime calculation” on page 9

• “Communication converter,” (item 4) on page 13

• “Resetting automatic operation on the generator” on page 20

• “Generator” on page 37

• “Fuel Alarm Limits” on page 44

Note

If your installation includes a secondary utility source, the APC Field Service Engineer

performing your start-up will configure your ATS to operate with two utility sources.