Installation, Ventilation – Blodgett DFG-100 XCEL User Manual

Page 10

Advertising
background image

8

Installation

DiRECt FLUE ARRAnGEMEnt
When the installation of a mechanically driven exhaust

hood is impractical the oven may be vented by a direct

flue arrangement.

WARninG!!

It is essential that the direct flue be installed

as follows. incorrect installation will result in

unsatisfactory baking and oven damage.

The flue must be class B or better with a diameter of 6”

(15 cm) for single ovens and 8” (20 cm) for double stacked

ovens. The height of the flue should rise 6-8 ft (2-2.5 m)

above the roof of the building or any proximate structure.

Never direct vent the oven into a hood. The flue should be

capped with a UL Listed type vent cap to isolate the unit

from external environmental conditions.
The direct vent cannot replace air consumed and vented

by the oven. Provisions must be made to supply the room

with sufficient make-up air. Total make-up air require-

ments for each oven section should be approximately 30

CFM (.85 m3) per section. To increase the supply air en-

tering the room, a ventilation expert should be consulted.

installing the draft hood
Ovens ordered for direct venting are supplied with a draft

hood. Install the draft hood as follows:
1. Place the draft hood over the flue connector.
2. Secure both ends with the sheet metal screws pro-

vided.

Flue

Drafthood

Front of

Oven

Figure 8

ventilation

Advertising