Press – APC SYMMETRA PDUM160H-B User Manual

Page 16

Advertising
background image

Operation: Operation Procedures

10

Symmetra PX 160 kW 400 V Operation

990-3015-001

Set the Q2 switch on the PDU-XR to the OFF

position.

Turn the UPS off using the display.

Set the Q1 switch on the PDU-XR to the OFF

position.

Set the Q5 switch on the PDU-XR to the OFF

position.

Set the

UPS

S

YSTEM

E

NABLE

switch to the OFF

position.

Set the

DC D

ISCONNECT

switch on all of the XR Battery enclosures and the PDU-XR to the OFF

position.

Press

Press

Press

Press

UPS

Alarms

Power Dist
Switch Gear
Environment

Log
Admin
Help

UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration

Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep

Notify PowerChute?
Cancel
Yes, Notify Servers
No, Don’t Notify

Turn UPS Off With
Server Notification?
>NO, ABORT
>YES, Turn UPS Off

Turning UPS off,
please wait...

Advertising