AMX RDM-3FDB User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-3FDB Triple Channel Lutron FDB Ballast Dimmer

1900 W

The RDM-3FDB Triple Channel Ballast Dimmer is a 1920 W positive air gap
relay and dimmer, built for strength and for reliable switching/dimming of
Lutron FDB ballasts. It is designed for use with the RDA series of enclo-
sures, in an AMX Lighting™ modular digital dimming system. The RDM-
3FDB module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.

RDM-3FDB UL and C-UL Ratings

120 VAC, 1920 W

240/277 VAC, 1920 W

Suggested Dimmed Loads

Most 3-wire dimmable fluorescent ballasts

Lutron

©

Hi-Lume

®

FDB Ballasts

Lutron Eco-10

®

Dimmable Ballasts

Specifications

Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.99 cm)

Dimmed output protected by a 250 mA GMA 5 x 20 mm fuse

Phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 20 in-lbs. (2.3 N/M)

Max. wire size: 10 AWG (4 mm²)

Weight: 1.57 lbs. (0.712 kg)

BTU/hr: 5

Control current: 85 mA @ 12 VDC

For use with FDB ballasts

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-3FDB to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-3FDB

Relay

Line in (hot)
Switched out

Dimmed out

Fuse

Positive air
gap relay

Relay

Line in (hot)
Switched out

Dimmed out

Low-voltage control wiring:
4-pin connector to AMX
Lighting master controller

Mounting
points

Ballast A

Ballast B

Relay

Line in (hot)
Switched out

Dimmed out

Ballast C

FIG. 2 RDM-3FDB connections

FIG. 3 RDM-3FDB wiring configuration

Pin 3 (RLY)

Pin 2 (DIM)

Pin 1 (+12 V)

RDM-3FDB 4-pin module connector

3 (-)

2 (AC)

1 (+)

4-pin plug from RDM series module

Note: The 4-pin plugs from the module connector
to the 4-pin connector on the master (black plug cover facing up).

BALLAST

Ballast

Circuit breaker
panel

Line in (HOT)

Switched

Dimmed

Florescent
Ballast

Neutral

Neutral

All neutrals are
common to the
Neutral block in the
enclosure. Provide a
separate neutral for
each load.

The fuses protect the dimming
circuit from a low impedance
load.

The fuse would blow if it

were incorrectly wired

Catastrophic ballast failure

Reversing switched and

dimmed circuits

Reversing dimmed and

line circuits.

The dimmed output must be
connected to a high impedance
load.

Advertising