AMX Dual Incandescent Dimmer Module RDM-2INC User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-2INC Dual Incandescent Dimmer Module

2400 W (x2)

The RDM-2INC Dual Incandescent Dimming Module 2400 W (x2) incan-
descent dimmer is designed for use with the RDA series of enclosures, in
an AMX Lighting™ modular digital dimming system. It can dim incandes-
cent lights, cold-cathode, neon and two-wire dimmable ballasts. The mod-
ule's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.

RDM-2INC UL and C-UL Ratings

•

120 VAC, 50/60 Hz, 2400 W

•

240/277 VAC, 50/60 Hz, 2400 W

Suggested Dimmed Loads

•

Incandescent

•

Low-voltage

•

Neon, cold-cathode

•

Two-wire, phase-controlled ballast

Specifications

•

Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.99 cm)

•

Phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 7 in-lbs. (0.8 N/M)

•

Max. wire size: 10 AWG (4 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 6.5 lbs. (2.948 kg)

•

BTU/hr: 600

•

Control current: 45 mA @ 12 VDC per dimmer, 90 mA total

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper temrnials.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Use low voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

Run all low-voltage and control wires away from heat producing parts

of the dimmer.

•

Each dimming circuit must have a separate neutral connection.

•

All electrical ratings are for continuous duty.

•

AC lighting loads only.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-2INC to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-2INC

Low-voltage
control wiring:
4-pin connectors
to AMX Lighting
master controller

350 µS choke

Dual 20 A power device

Line out

Line in (hot)

High-voltage
connections

Mounting
points

FIG. 2 RDM-2INC connections

FIG. 3 RDM-2INC wiring application

Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)

RDM-2INC four-pin module connector

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

2 (-)

1 (+)

Light A Light B

(B) Load

(A) Load

(B) Line in (HOT)

(A) Line in (HOT)

(A) Neutral

(B) Neutral

Neutral

Load

Load

Neutral

Neon lights

(cold-cathode, on/off)

Two-wire dimmable

ballast

Circuit breaker

panel

Advertising