AMX Incandescent Dimmer Module RDM-INC50 User Manual

Installation sheet

Advertising
background image

Installation Sheet

RDM-INC50 Incandescent Dimmer Module

6000 W

The RDM-INC50 Incandescent Dimmer Module is a standard 6000 W
incandescent dimmer. It can dim incandescent lights, cold-cathode, neon
transformers and two-wire dimmable ballasts. It is designed for use with the
RDA series of enclosures, in a AMX Lighting™ modular digital dimming
system. The RDM-INC50 module's 120, 240, and 277 VAC ratings are CE,
UL, and C-UL approved.

RDM-INC50 UL and C-UL Ratings

•

120 VAC, 6000 W

•

240/277 VAC, 6000 W

Suggested Dimmed Loads

•

Incandescent

•

Low-voltage

•

Neon, cold cathode

•

Two-wire, phase-controlled ballast

Specifications:

•

Dimensions (HW): 10.0" x 5.50" (25.4 cm x 13.97 cm)

•

Phase dependant

•

Use wires rated at 75°C (167°F)

•

Torque terminals to 16 in-lbs. (1.84 N/M)

•

Max. wire size: 8 AWG (10 mm²)

•

Wire stripping length: 0.28" (7 mm)

•

Weight: 7.0 lbs. (3.175 kg)

•

BTU/hr: 750

•

Control current: 45 mA @ 12 VDC

•

Occupies two enclosure spaces

Caution: Pre-Installation Notes

•

All Class 1 wiring must be connected to proper terminals.

•

All control wiring must be connected to proper terminals.

•

Disconnect power while installing or connecting the unit.

•

Keep top and bottom air vents clear at all times.

•

Test loads for shorts before connecting.

•

Run all control and low-voltage wires away from heat producing parts

of the dimmer.

•

Each dimming circuit must have a separate neutral connection.

•

Use low-voltage wires with a 300 volt rating or greater.

•

Use field installed copper conductors.

•

All electrical ratings are for continuous duty.

•

AC lighting loads only.

•

For indoor use only.

•

This module may require extra power from the AXlink connection or an

external power supply connected to the control card.

Connecting the RDM-INC50 to the AMX Lighting Master

Lighting Application Drawing

FIG. 1 RDM-INC50

Line in (hot)

Load out

500µS choke

50 A Power
Device

Mounting
points

Low-voltage control
wiring: 4-pin connector
to AMX Lighting
master controller

FIG. 2 RDM-INC50 connections

FIG. 3 RDM-INC50 wiring application

Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)

RDM-INC50 4-pin module connector

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

2 (-)

1 (+)

Neutral

Load

Neutral

Load

Neon lights

(cold-cathode, on/off)

Two-wire

dimmable ballast

Neutral

Line in (HOT)

Load

All neutrals are common to the
Neutral block in the enclosure.
Provide a separate neutral for
each load.

Advertising