SPECIFICATIONS

Input Power

115 Volt/ 60Hz, 115 Volt/ 50Hz, 230 Volt/ 60 Hz, or 230 Volt/
50Hz

Input Current

200ma nominal, 2 amperes (short circuit)

Stroke Length Control

0 – 100% control range
Resolution – 0.0625% increments

Stroke Adjustment response

Approximately 1% per second

Analog Input

Operating Range

0 to 25.5mA (4-20 mA factory default)

Input Impedance

160 ohms

Minimum Span

2.0 mA

Isolation

500V from all other inputs, outputs and ground, optically
isolated

Conditioning

8 second running average.

Split Ranging and Reverse Acting accessible via calibration.

Analog Output

Operating Range

0 to 25.5mA (4-20 mA factory default)

Maximum Load

700 ohms

Minimum Span

2.0 mA

Conditioning

None. Output represents current stroke position.

Split Ranging and Reverse Acting accessible via calibration.

Isolation

500V from all other inputs, outputs and ground, optically
isolated.

Status Input

Motor On/Off

Optically isolated dry contact input. Open contact indicates
motor is off. Controller will then suspend all stroke control
action. Motor starter should provide a contact for connection
here.

Environmental

Rated Ambient Temperature

-20

°C to 40°C (-4°F to 104°F)

Storage Ambient Temperature

-25

°C to 60°C (-13°F to 140°F)

Enclosure

NEMA4, IP66, NEMA 4X

Approvals

UL/ULC - NEMA 4X
CE – IEC EN 61010-1

Transient Voltage

Max Impulse withstand 1500V (115VAC Models), 2500V
(230VAC Models) at 50uS

Voltage Overload

120% Continuous,

Pollution Degree

Suitable for Pollution Degree 3

Input Voltage

115 (105-125 acceptable range) or 230 (208 – 240 acceptable
range) VAC
Note: factory configured only for correct input voltage range
(specified at time of purchase) Single phase input only 50 or 60