Power-up options summary – Pulsafeeder Pulsar ECA NEMA4X User Manual

Page 32

Advertising
background image

Hz. Input frequency range 48 Hz to 62 Hz

Altitude:

3300 Ft (1000 M) above sea level (de-rate 5% per additional
3300 Ft)

Humidity

0-90% (non-condensing)

Temperature

0° C (32° F) Minimum operating temperature
40° C (104° F) Maximum operating temperature

Earth Leakage Current

Size Earth Leakage Circuit Breakers (ELCB) to a detection
level of 30 mA or greater

Fuse

One Power input fuse (AC over current protection) is located on
the main control board. This fuse is a 2 amp slow-blow type
(Schurter 34.6618, Digikey 486-1138-ND. The fuses should be
checked after any failure of the unit to power up properly.


12.

POWER-UP OPTIONS SUMMARY


Upon application of input power, the ECA will perform certain functions if the pushbuttons are used, as
follows:

Pushbuttons
pressed at power-
up

Function

Reference

Section

NONE

Normal operation, use all calibration data from memory

BLACK key

Forces a mechanical zero position calibration

Mechanical

Zero

Calibration

WHITE key

Initiates self-test with jumpers

Self-Test

Mode

BOTH keys (WHITE
and BLACK)

Resets all to factory default values, performs an
automatic mechanical zero calibration, analog signals
will require re-calibration

Error

Recovery










26