Addr – NOVUS N322 User Manual

Page 2

Advertising
background image

of1

Off time 1

Off time 1 - Defines the minimum off time for control OUTPUT 1. Once

OUTPUT 1 is turned off, it remains so for at least the time programmed

in of1. For thermocouple inputs this parameter is not available. This

parameter is intended for refrigeration systems where longer

compressor life is desired. For heating systems, program of1 to zero.

Value in seconds, 0 to 999 s.

on1

on time 1

On time 1 - Defines the minimum on time for control OUTPUT 1. Once

turned on, OUTPUT 1 remains so for at least the time programmed in
on1

. For thermocouple inputs this parameter is not available. This

parameter is intended for refrigeration systems where increased

compressor life is desired. For heating systems, program on1 to zero.

Value in seconds, 0 to 999 s.

dl1

Delay 1

Delay 1 - Delay time to start control. Upon power-on, control OUTPUT 1 is

kept off until the time programmed in dl1 is elapsed. Its usage is

intended to prevent multiple compressors to start simultaneously after
the turn-on of a system with several controllers. Value in seconds, 0 to

250 s.

of2

Off time 2

Off time 2 - Defines the minimum off time for control OUTPUT 2. Once

OUTPUT 2 is turned off, it remains so for at least the time programmed

in of2. For thermocouple inputs this parameter is not available. This

parameter is intended for refrigeration systems where increased

compressor life is desired. For heating systems, program on2 to zero.

Value in seconds, 0 to 999 s.

on2

on time 2

On time 2 - Defines the minimum on time for control OUTPUT 2. Once

turned on, OUTPUT 2 remains so for at least the time programmed in
on2

. For thermocouple inputs this parameter is not available. This

parameter is intended for refrigeration systems where increased

compressor life is desired. Value in seconds, 0 to 999 s. For heating

systems, program of2 to zero.

dl2

Delay 2

Delay 2 - Delay time for OUTPUT 2 to turn on relative to OUTPUT 1.

This parameter defines a particular working mode, typically used in

multiple stage systems, where OUTPUT 2 is allowed to go on only if

OUTPUT 1 is already on for at least dL2 seconds. Also, OUTPUT 2 is

driven off whenever OUTPUT 1 goes off. dL2= 0 disables this

function. Value in seconds, 0 to 250 s.

Addr

Address

Address - Controllers with the optional RS485 Modbus RTU

communication interface have the Addr parameter at the Configuration

level. Set a unique Modbus address for each equipment connected to the

network. Address range is from 1 to 247.

Level 3 – Calibration level
The controller is factory calibrated. The following parameters should be accessed only
by experienced personnel. To enter this cycle, the

key must be kept pressed for 4

seconds.

Don’t press the

and

keys if you are not sure of the calibration

procedures. Just press the

key a few times until the temperature

measurement level is reached again.

pas

Password - Enter the correct password to unlock write operations for

the parameters in the following levels.

[Al

Calibration low - Offset value of the input. It adjusts the lower

measurement range of the sensor.

[Ak

Calibration High - Gain calibration. It adjusts the upper measurement

range of the sensor.

[JL

Cold Junction Offset calibration - This parameter is available only

for thermocouple.

FA(

Factory Calibration - Restores factory calibration parameters. Change

from 0 to 1 restores the calibration parameters with factory values.

Prt

Protection - Defines the levels of parameters that will be password

protected. See "Configuration Protection" for details.

Pa(

Password Change - Allows changing the current password to a new

one. Values from 1 to 999 are allowed.

Sn2

Serial number - First part of the controller electronic serial number.

sn1

Serial number - Second part of the controller electronic serial number.

sn0

Serial number - Third part of the controller electronic serial number.

WORKING WITH THE CONTROLLER

Multiple output controllers are suited for controlling multiple stage systems.
Other applications require OUTPUT 1 to be the control output and OUTPUT 2 to be the

alarm.
There are eight distinct alarm functions implemented in OUTPUT 2, selected by the

parameter Ac2, described below:

2

- Low temperature alarm – OUTPUT 2 is turned on when the measured

temperature falls below the SP2 value.

3

- High temperature alarm – OUTPUT 2 is turned on when the measured

temperature exceeds the value programmed in SP2.

4

- Inside range alarm – OUTPUT 2 is turned on when the measured

temperature is within the range defined by:

(SP1 SP2) and (SP1 + SP2)

5

- Outside range alarm: OUTPUT 2 is turned on when the temperature falls

outside the range defined by:

(SP1 SP2) and (SP1 + SP2)

Functions 6, 7, 8 e 9 are identical to the above ones except that they incorporate the Initial

Blocking feature, which inhibits the output if an alarm condition is present at start-up. The

alarm will be unblocked after the process reaches a non-alarm condition for the first time.
In a multiple stage application, SP1 and SP2 are configured to operate at different

temperatures, creating a progressive sequence for turning on the outputs

(compressors) in response to a system demand. The output delays for turning on the

compressors (dL1 and dL2) cause the compressors to be turned on one by one,

minimizing energy demand.
Another usage for multiple output controllers is in systems that require automatic

selection between cool and heat action. In these applications, one output is configured

as reverse action (heating) and the other as direct action (refrigeration). The output

status led P1 and P2 in the controller panel, signals when the control output in on.

CONFIGURATION PROTECTION

A protection system to avoid unwanted changes to the controller parameters

is implemented. The level of protection can be selected from partial to full. The following

parameters are part of the protection system:
Pas

When this parameter is presented, the correct password should be entered to

allow changes of parameters in the following levels.

Prt

Defines the level of parameters that will be password protected:

1 - Only calibration level is protected (factory configuration);
2 - Calibration and Configuration levels are protected;
3 - All levels are protected - calibration, Configuration and setpoints.

PA(

Parameter for definition of a new password. Since it is located in the calibration

level, can only be changed by a user that knows the current password. Valid

passwords are in the range 1 to 999.

Configuration protection usage
PAS

parameter is displayed before entering a protected level. If the correct password is

entered, parameters in all following levels can be changed. If wrong or no password is

entered, parameters in the following levels will be read only.
Important notes:
1- After five consecutive attempts to enter a wrong password, new tentative will be

blocked for the next 10 minutes. If the current valid password is unknown, the master

password can be used only to define a new password for the controller.

2 - The password for a brand new device is 111.

MASTER PASSWORD

The master password allows user to define a new password for the controller, even if

the current password is unknown. The master password is based in the serial number

of the controller, and calculated as following:

[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of SN0 ]

For example the master password for the device with serial number 987123465 is: 1 9 3 6

as follows: 1 + sn2= 987; sn1= 123; sn0= 465 = 1 + 9 + 3 + 6

How to use the master password:
1- Enter the master password value at PaS prompt.
2- Go to PA( parameter and enter the new password, which must not be zero (0).
3- Now you can use this new password to access all controller parameters with modify

rights.

ERROR MESSAGES

Sensor measurement errors force the controller outputs to be turned off. The cause for

these errors may have origin in a bad connection, sensor defect (cable or element) or

system temperature outside the sensor working range. The display signs related to

measurement errors are shown below:

Measured temperature exceeded maximum allowed range for the

sensor. Broken Pt100, Pt1000 or T/C. Short circuited NTC sensor.

Measured temperature is below minimum measurement range of the

sensor. Short circuited Pt100, Pt1000 or T/C. Broken NTC.

WARRANTY

Warranty conditions are available on our web site

www.novusautoamtion.com

.