9 specifications, Ac input – APC VS 50 User Manual

Page 58

Advertising
background image

Magnum VS –48 Vdc User’s Manual

Page 53

9 Specifications


The overall system specifications can vary, depending upon the number of rectifier modules.
Note that some specification items are provided on a “per rectifier” basis and must be combined
or totaled for a given system configuration.

9.1. AC Input


TWF0500H54B Rectifier

Input Voltage Range

85 – 264 Vac

AC Frequency Range

47 – 63 Hz

Apparent Power Factor

99% Typical, 98% Minimum

Input Current (per Rectifier)

5.5 A @ 115Vac
3.7 A @ 230Vac

Turn on Time

2 Seconds

Magnum VS 50 Power System

Input Voltage Range

85 – 264 Vac

AC Frequency Range

47 – 63 Hz

Apparent Power Factor

99% Typical, 98% Minimum

Input Current

27.5 A @ 115 Vac
18.5 A @ 230 Vac

Advertising