APC VS 50 User Manual
Page 60

Magnum VS –48 Vdc User’s Manual
Page 55
Magnum VS 50 Power System
Output Voltage (factory
programmed)
54.0 Vdc
Operating Voltage Range
47 – 56.5 Vdc
Rated Output Current
50 A
Efficiency 85%
Typical
Over Voltage Protection
59.5 Vdc
Output Current
45 A Minimum Continuous at 115 Vac Input
52.5 A Minimum Continuous at 230 Vac Input.
Current Limit
46.5 A Maximum at 115 Vac Input
55.0 A Maximum at 230 Vac Input.
Power Output @ 54.5 Vdc
2450 W Continuous at 115 Vac Input
2850 W Continuous at 230 Vac Input
Magnum VS 100 Power System
Output Voltage (factory
programmed)
54.0 Vdc
Operating Voltage Range
47 – 56.5 Vdc
Rated Output Current
100 A
Efficiency 91%
Typical
Over Voltage Protection
59.5 Vdc
Output Current
90 A Minimum Continuous at 115 Vac Input
105 A Minimum Continuous at 230 Vac Input.
Current Limit
93 A Maximum at 115 Vac Input
110 A Maximum at 230 Vac Input.
Power Output per Rectifier
@ 54.5Vdc
4900 W Continuous at 115 Vac Input
5700 W Continuous at 230 Vac Input