Type b gas vent liner system, Flex extensions – DuraVent DuraFlex AL Installation User Manual

Page 12

Advertising
background image

12

sealing the Top Plate to the masonry

chimney using the non-hardening

sealant, slide the B-Vent Storm Collar

over the length of B-Vent pipe, until

the proper length of pipe extends

above the chimney. Always have a

minimum of 12 inches of B-Vent pipe

below the Top Plate for stability. It is

preferable to extend the B-Vent pipe

down within the masonry chimney to

the roof line level so as to keep the

flue gas hot in the exposed portion

of the masonry chimney. Attach the

Storm Collar to the B-Vent pipe with

(4) 3/8-inch long sheet metal screws

equally spaced at 90°. The Storm

Collar rests on the Top Plate and

serves as the top support for the liner

system, and is UL Listed to support

up to 50 feet of Flex or B-Vent Liner.

Refer to Figure 17.

Step 4. Seal the Storm Collar to the

Top Plate and twist-lock the B-Vent top

to the B-Vent pipe. As an alternative

to the standard cap, you may want

to install a B-Vent High-Wind Top in

areas where excess wind may be a

concern (Figures 17 & 18).

Step 5. For improved draft, the vent

may be extended in height above the

top of the masonry chimney by simply

adding additional lengths of B-Vent

Pipe. If the vent is more than 3 feet

above the top of the chimney, secure

it with a locally fabricated brace, as

shown in Figure 18.

TYPE B GAS VENT LINER SYSTEM

For exterior chimneys in cold

climates, an air insulated, double-

wall Type B Gas Vent Liner system

is recommended, particularly for

fan-assisted gas appliances, which

have a greater tendency to produce

corrosive condensation when flue

gases are permitted to cool in the

vent system. To install a 100% Type

B Gas Vent Liner, use a Type B Gas

Vent Termination and Pipe Lengths, in

combination with a Type B Gas Vent

Tee for this installation.

In the event that the exterior masonry

chimney has an offset, it will be

necessary to feed Flexible Liner down

through the offset, with Type B Gas

Vent to be used above the offset.

FLEX EXTENSIONS

For tall chimney installations where

more than one length of flex is

required, additional Flex may be

Figure 19

Figure 18

OPTIONAL HIGH

WINDCAP

STANDARD

CAP

SUPPORT

FLex LINeR

FLex COUPLING

SHeeT MeTAL

SCReWS