Prior to installation, Chimney liner selection – DuraVent DuraFlex AL Installation User Manual

Page 5

Advertising
background image

5

Figure 1

Figure 2

For complete sizing instructions, refer

to the National Fuel Gas Code , the

International Fuel Gas Code, or the

DuraVent Sizing Handbook. Failure

to properly size the venting system

may result in draft hood spillage, back

pressure, and corrosive condensation

in the relining system.

As an alternate method, for draft

hood-equipped appliances and

decorative gas fireplaces only, the

venting system may be sized to the

outlet of the appliance. For two or

more draft hood-equipped appliances,

the effective area of the vent shall not

be less than the area of the largest

appliance, plus 50% of the areas

of additional draft hood outlets. For

fan-assisted gas appliances, the vent

system must be sized using the sizing

instructions and tables referenced

above.

PRIOR TO INSTALLATION

Before installing the Chimney Liner

System, the chimney passageway

should be examined to ascertain that

it is clear and free of obstructions,

and must be cleaned if it has been

previously used for venting solid or

liquid-burning appliances or fireplaces.

CHIMNEY LINER SELECTION

The basic DuraFlex AL Chimney

Liner System consists of a continuous

flexible liner from the top of the

chimney to the appliance connection

(Figure 1). This system is relatively

easy to install, even in masonry

chimneys that are constructed with an

offset. This single-wall flexible system