WIKA AC-1 User Manual

Page 16

Advertising
background image

16

WIKA operating instructions pressure transmitter model AC-1

14026285.01 11/2012 GB/D/F/E

GB

6. Commissioning, operation

6. Commissioning, operation

CAUTION!

Prior to commissioning, the pressure transmitter must be subjected to a visual inspection.

Only use the pressure transmitter if it is in perfect condition with respect to safety.

6.1 Mechanical mounting

■

The sealing faces at the instrument have to be undamaged and

clean.

■

When screwing the instrument in, the force required to do this must

not be applied through the casing, but only through the spanner flats

provided for this purpose and using a suitable tool.

The correct torque depends on the dimensions of the process

connection and the gasket used (form/material).

Do not exceed the following tightening torque:

max. 30 Nm

■

When screwing in, do not cross the threads.

■

For information on tapped holes and welding sockets, see Technical Information IN 00.14 at

www.wika.com.

Spanner flats