6. Commissioning, operation

6.1 Mechanical connection

In accordance with the general technical regulations for pressure and tempera-

ture measuring instruments (e.g. EN 837-2 or EN 13190). When screwing the

gauges in, the force required to do this must not be applied through the case

or the cable terminal box, but only through the spanner flats provided for this

purpose and using a suitable tool.

6. Commissioning, operation

Installation with

open-ended spanner

With safety pressure gauges (see dial symbol k) ensure that the free space

behind the blow-out back is at least 15 mm.

Special requirements for the installation point

To avoid, amongst other things, switch signal "chatter", it must be ensured

that the instruments are mounted free of vibration. If the measuring point is not

adequately stable, a measuring instrument holder should be used for fastening

(and possibly via a flexible capillary).

If vibrations cannot be avoided by means of suitable installation, instruments

with liquid filling should be used.

The instruments should be protected against coarse dirt and wide fluctuations in

ambient temperature.

6.2 Electrical connection

The electrical connection must only be made by qualified skilled personnel. The

permissible electrical data, connection details and switching functions are given

on the product label affixed to the instrument.
The connection terminals are appropriately marked.

The instruments must be connected to the equipotential bonding of the plant.

The electrical connection is made via a DIN EN 175301-803 connector.