Commissioning, operation / 7. maintenance and, Maintenance and cleaning – WIKA 851 User Manual

Page 12

Advertising
background image

GB

2435182.03 12/2010 GB/D/F/E

WIKA operating instructions electronic contact, model 830 E

12

6.3 Adjusting the set pointers

The setting of the set points is achieved using the adjustment lock in the

window with the aid of the adjustment key (part of the scope of delivery; found in

standard instruments on the side of the terminal box).

6. Commissioning, operation / 7. Maintenance and ...

Set pointer

Adjustment lock

The set pointers for the limit switches are freely adjustable over the full scale

range. For reasons of switching accuracy and long life of the mechanical

measuring systems, the switch points should be between 10 % and 90 % of the

measuring span.

7. Maintenance and cleaning

7.1 Maintenance

The instruments are maintenance-free.

The indicator and switching function should be checked once or twice every

year.

The instrument must be disconnected from the process to check the indication

and switching function with a pressure or temperature testing device.

Repairs must only be carried out by the manufacturer or appropriately qualified

skilled personnel.

7.2 Cleaning

CAUTION!

Prior to cleaning, disconnect the instrument from the mains.

Clean the instrument with a moist cloth (in soapy water).

Ensure that all the parts are dry before the power is switched on

again.

Removable

adjustment key