Operating Instructions Temperature Indicating Controller CF1M

V1.

1

03/200

5

- 18 -

Option: Heater burnout alarm output

(1) This alarm is not available for

detecting current under phase control.

(2) Use the current transformer (CT) supplied

and pass one lead wire of heater circuit
into the hole of the CT.

(3) When wiring, keep CT wire away

from AC source and load wire to
avoid external interference.

[Fig. 7-2]

8. Specifications

8.1 Standard specifications

Mounting method : Flush
Setting

: Input system by using membrane sheet key

Display

: Red LED display 4 digits, size, 8(H) x 4(W)mm

Accuracy (Setting and indicating)

Thermocouple

: Within ±0.3% of input range full scale ±1 digit,

or 2°C (4°F) whichever is greater

RTD

: Within ±0.2% of input range full scale ±1 digit

or 1°C (2°F) whichever is greater

Scaling range

K

: 0 to 1370°C

(0 to 2500°F)

J

: 0 to 1000°C

(0 to 1800°F)

E

: 0 to 800°C

(0 to 1500°F)

PL-

: 0 to 1390°C

(0 to 2500°F)

N

: 0 to 1300°C

(0 to 2300°F)

Pt100 : -199.9 to 850.0°C (-199.9 to 999.9°F), -200 to 850°C (-300 to 1500°F)
JPt100 : -199.9 to 500.0°C (-199.9 to 900.0°F), -200 to 500°C (-300 to 900°F)

Input sampling period: 0.25 seconds
Input

Thermocouple

: K, J, E, PL- , N

External resistance, 100

Ω or less

When input burnout, Upscale

RTD

: Pt100, JPt100 3-wire system

Allowable input lead wire resistance, 10Ω or less per wire
When input burnout, Upscale

Control output

Relay contact

: 1a

Control capacity,

250Vac 3A (resistive load)
250Vac 1A (inductive load cosø=0.4)

Non-contact

: For SSR drive

voltage

12

+2

,

0

Vdc Maximum 40mA (short circuit protected)

Current

: 4 to 20mAdc

Load resistance, maximum 500

Supply voltage

: 100 to 240Vac, 50/60Hz, 24Vac/dc, 50/60Hz

Allowable voltage : In the case of 100 to 240Vac, 85 to 264Vac
fluctuation

In the case of 24Vac/dc, 20 to 28Vac/dc

CT input

terminal

Power source

Heater

CT

8
9