Operating Instructions Temperature Indicating Controller CF1M

V1.

1

03/200

5

- 19 -

Temperature alarm output

The alarm action point is set by ± deviation to the main setting (except Process value alarm).

[When the alarm action is set as energized]

When the input exceeds the range, the output turns ON or OFF
(in the case of High/Low limit range alarm).

[When the alarm action is set as deenergized]

The output acts conversely.

• Setting accuracy

Thermocouple : Within ±0.3% of input full scale ±1 digit, or ±2°C (4°F) whichever is greater
RTD

: Within ±0.2% of input full scale ±1 digit

• Action

: ON/OFF action

Hysteresis, 0.1 to 100.0°C (°F)

• Output

: Open collector

Control capacity, 24Vdc 0.1A (maximum)

Loop break alarm output

When manipulating value is in its maximum or minimum status, the alarm is activated if the
process variable does not change at a rate higher than the setting span within the setting time.

Detects Heater burnout, Sensor burnout and Abnormality at operation end.

Output: Open collector

Control capacity, 24Vdc 0.1A (maximum)

Control action

PID action (with auto-tuning function)
PD action (with auto-reset function) (When I value is set to 0.)
P action (with auto-reset function) (When I and D values are set to 0.)
ON/OFF action (When P value is set to 0 or 0.0.)

Proportional band : 0 (0.0) to rated scale maximum value
Integral time

: 0 to 3600s (off when set to 0)

Derivative time

: 0 to 3600s (off when set to 0)

Proportional cycle : 1 to 120s
ARW

: Automatic

Output limit

: 0 to 100% (For the Current output type, -5 to 105%)

Hysteresis

: 0.1 to 100.0°C (°F)

Circuit insulation configuration

* If the control output type is current or non-contact voltage output, between

the communication and output is non-isolated.