Operating Instructions Temperature Indicating Controller CF1M

V1.

1

03/200

5

- 8 -

Output ON/OFF action hysteresis setting
• Sets the ON/OFF action hysteresis of control output.
• This setting item is available only for the ON/OFF action.
• 0.1 to 100.0°C

1.0°C

Event output function selection
• One of the functions is selectable from Temperature alarm,
Loop break alarm or Heater burnout alarm.
• Heater burnout alarm can be selected only when option [W1X] is

applied.

• Temperature alarm output

:

Loop break alarm output

:

Heater burnout alarm output (option):
Temperature alarm action selection
• Selects temperature alarm action.
• No alarm

:

High limit alarm

:

High limit alarm w/standby

:

Low limit alarm

:

Low limit alarm w/standby

:

High/Low limits alarm

:

High/Low limits alarm w/standby

:

High/Low limit range alarm

:

High/Low limit range alarm w/standby :
Process high alarm

:

Process high alarm w/standby

:

Process low alarm

:

Process low alarm w/standby

:

No alarm

Temperature alarm energized/deenergized selection
• Sets the temperature alarm output as energized or deenergized.
• This setting item is not available if Temperature alarm output

is not selected in Event output function selection, nor if No alarm is
selected in Temperature alarm action selection.

• Energized :
Deenergized :

Energized

Temperature alarm hysteresis setting
• Sets hysteresis value for temperature alarm.
• This setting item is not available if Temperature alarm output is not

selected in Event output function selection, nor if No alarm is selected
in Temperature alarm action selection.

• 0.1 to 100.0°C

(°F)

1.0°C

(°F)

Temperature alarm delayed timer setting
• Sets the action delayed timer for temperature alarm.

Alarm output works past the setting time after the input value
reaches the alarm output range.

• This setting item is not available if Temperature alarm output is not

selected in Event output function selection, nor if No alarm action
is selected in Temperature alarm action selection.

• 0 to 9999 seconds

0s

Main setting value rising rate setting
• Sets the rising rate of main setting value. (Rising value per minute)
• 0 to 9999°C /min. (°F /min.)
With decimal point, 0.0 to 999.9°C /min. (°F /min.)

0°C /min.

Main setting value falling rate setting
• Sets the falling rate of main setting value. (Falling value per minute)
• 0 to 9999°C /min. (°F /min.)
With decimal point, 0.0 to 999.9°C /min. (°F /min.)

0°C /min.