WIKA A2G-45 User Manual

Page 8

Advertising
background image

WIKA operating instructions air2guide model A2G-45

GB

8

40389228.01 09/2012 GB/D/F/E/I

4. Design and function / 5. Transport, packaging ...

4. Design and function

4.1 Description
Design

CE conformity:

2004/108/EC electromagnetic compatibility

2002/95/EC RoHS (restriction of the use of certain hazardous

substances in electrical and electronic equipment)

Accuracy class

1.5 %

Measuring ranges

Variant 1: -500 ... +500 Pa (-100 .. +100 Pa, -250 ... +250 Pa,

-300 ... +300 Pa to be set via jumper) or

Variant 2: 0 ... 2,500 Pa (0 ... +100 Pa, 0 ... +250 Pa, 0 ... +1,000 Pa

to be set via jumper)

Pressure limitation

Maximum pressure: 25 kPa

Permissible temperature

Ambient: -20 … +70 °C

Operation: -10 … +50 °C

(-5 … +50 °C with automatic zero adjustment)

4.2 Scope of delivery

Cross-check scope of delivery with delivery note.

5. Transport, packaging and storage

5.1 Transport

Check the differential pressure switch for any damage that may have

been caused by transport. Obvious damage must be reported immedi-

ately.