Bryant 541A User Manual

Page 10

Advertising
background image

E. Control Circuit Wiring

Unit internal control circuit voltage is 24 volts. See Table 8
for recommended thermostats. Connect thermostat assembly
and other accessories as shown in unit label diagram and
Fig. 10. Refer to installation instructions shipped with in-
door unit. See Fig. 11 for field-supplied airflow switch wiring
if airflow switch is used. The control wiring entrance is lo-
cated on right corner post of 541A unit. See Fig. 1. Wiring
connects to a terminal block located at extreme right of con-
trol box.

Transformers no. 1 and 2 are wired for a 230-v unit. If a 208/
230-v unit is to be run with a 208-v power supply, the trans-
formers must be rewired as follows:

1. Remove cap from red (208 v) wire.

2. Remove cap from orange (230 v) spliced wire.

3. Replace orange wire with red wire.

4. Recap both wires.

IMPORTANT:

BE CERTAIN UNUSED WIRES ARE CAPPED.

Failure to do so may damage the transformer.

Route thermostat cable or equivalent single leads of no. 18 AWG
(American Wire Gage) colored wire from subbase terminals
through conduit in unit to low-voltage connections as shown
on unit wiring diagram and Fig. 10.

NOTE:

For wire runs up to 50 ft, use no. 18 AWG insulated

wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insu-
lated wire (35 C minimum). For over 75 ft, use no. 14 AWG
insulated wire (35 C minimum). All wire larger than no. 18 AWG
cannot be directly connected to the thermostat and will re-
quire a junction box and a splice at the thermostat.

F. Electric Resistance Crankcase Heater

The crankcase heater is inserted into the compressor crank-
case. The crankcase heater is operated from the normally closed
contacts of the control relay (CR1) and is automatically
energized when compressor stops. This heater keeps crank-
case warm to prevent oil dilution by refrigerant, ensures good
lubrication, and minimizes loss of oil during start-up.

G. Airflow Switch

Bryant recommends an indoor airflow switch (field supplied)
be installed and interlocked with the outdoor unit. This pre-
vents the outdoor unit from operating if indoor airflow fails
(broken fan belt, etc.). Operation of the compressor in vacuum
can damage bearing surfaces. Install indoor airflow switch in
a convenient location at the indoor supply air duct and wire
per Fig. 11.

PRE-START-UP

IMPORTANT:

Before beginning Pre-Start-Up or Start-Up, re-

view Start-Up Checklist at the back of this book. The check-
list assures proper start-up of the system and provides a record
of unit condition, application requirements, system informa-
tion, and operation at initial start-up.

CAUTION:

Do not attempt to start the heat pump

system, even momentarily, until the following steps have
been completed. Compressor damage may result.

I. SYSTEM CHECK

1. Check all air handler and other equipment auxiliary

components. If unit has field-installed accessories, be
sure all are properly installed and correctly wired. If
used, airflow switch must be properly installed. See
Fig. 11.

2. Backseat (open) compressor suction and discharge valves.

Now close valves one turn to allow refrigerant pres-
sure to reach test gages.

3. Open liquid line service valve.

4. Check tightness of all electrical connections.

5. Compressor oil level should be visible in sight glass.

Adjust the oil level as required. No oil should be
removed unless the crankcase heater has been ener-
gized for at least 24 hours. See Start-Up section, Pre-
liminary Oil Charge on page 12.

6. Be sure unit is properly leak checked, dehydrated, and

charged. See Preliminary Charge, this page.

7. Electrical power source must agree with nameplate

rating.

8. Crankcase heater must be firmly locked into compres-

sor crankcase. Be sure crankcase is warm (heater must
be on for 24 hours before starting compressor).

9. Be sure compressor floats freely on the mounting springs

and that upper flat washers can be moved with fin-
ger pressure. See Compressor Mounting, page 2, and
Fig. 4 for loosening compressor bolts.

II. LEAK TEST AND DEHYDRATION

Leak test the entire refrigerant system using soap bubbles
and/or an electronic leak detector. Evacuate and dehydrate
entire refrigerant system by use of methods described in
GTAC II, Module 4, System Dehydration.

III. TURN ON CRANKCASE HEATER

Turn on crankcase heater for 24 hours before starting the unit
to be sure all refrigerant is out of the oil. To energize crank-
case heater, perform the following steps:

1. Set the space thermostat system switch to OFF, or ad-

just the temperature so there is no demand for cooling.

2. Close the field disconnect.

3. Leave the compressor circuit breaker off. The crankcase

heater is now energized.

IV. PRELIMINARY CHARGE

Refer to GTAC II, Module 5, Charging, Recovery, Recycling,
and Reclamation for charging methods and procedures. Charge
with R-22 by the liquid charging method (through liquid serv-
ice valve) on the high side. See approximate refrigerant charge
in Table 4. Charge according to the values in the Charging
Chart, Fig. 12 and 13, page 14.

V. THERMOSTAT ANTICIPATOR ADJUSTMENT

A. Heating/Cooling Thermostat (HH621606)

The thermostat has an adjustable heat anticipator for both
first- and second-stage heating circuits.

B. Settings

Set adjustment lever for first-stage anticipator at 0.79 (left-
hand side). Set adjustment lever for second-stage anticipator
(right-hand side) at 0.42.

C. Outdoor Thermostat

Refer to 524A-H accessory heater installation instructions for
details of this thermostat (if used).

—10—

Advertising