Table 7 — Electrical Data (3 Ph/60 Hz)

541A

UNIT

COMPRESSOR

FAN MOTORS (Single-Phase)

Model

Volts

MCA

ICF

MOCP

(Amps)

Fuse Only

RLA

LRA

Total
Fans

FLA (ea)

Fan No.

Name-

plate

Supplied*

Min

Max

1

2

120

501

208-230

187

253

62.5

178

100

43.6

170

2

4.3

3.7

601

460

414

528

29.1

81

40

20.0

77

2.3

1.9

180

501

208-230

187

253

87.5

274

125

63.6

266

2

4.3

3.7

601

460

414

528

40.7

124

60

29.3

120

2.3

1.9

LEGEND

FLA

Full Load Amps (fan motors)

ICF

Maximum Instantaneous Current Flow during start-up

(LRA of compressor plus total FLA of fan motors)

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps per NEC Section 430-24

MOCP — Maximum Overcurrent Protection (fuse only)
RLA

Rated Load Amps (compressor)

*Units are suitable for use on electrical systems where voltage supplied

to the unit terminals is not below or above the listed limits.

NOTES:
1. MCA and MOCP values are calculated in accordance with NEC

(National Electric Code), Article 440.

2. Motor RLA and FLA values are established in accordance with

UL (Underwriters’ Laboratories) Standard 1995.

EQUIP GND

21

22

23

13

12

11

DISCONNECT PER NEC
OR LOCAL CODE

TERMINAL BOARD (TB1) IN
UNIT CONTROL BOX

LEGEND

CAP

Capacitor

EQUIP — Equipment
GND

Ground

NEC

National Electrical Code

Field Wiring
Factory Wiring

Fig. 9 — Main Power Supply Wiring