Table 2 — Weight Distribution

UNIT
541A

WEIGHT — lb

Total

Operating

Weight

Support Point

(Fig. 3)

1

2

3

4

120

750

147

228

228

147

180

803

158

243

244

158

Table 3 — Maximum Vertical Separation*

OUTDOOR

UNIT
541A

INDOOR

UNIT

524A-H

DISTANCE — FT

Indoor Unit

Above Outdoor

Unit

Below Outdoor

Unit

120

120

50

50

180

180

80

80

*Vertical distance between indoor and outdoor units.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

LEGEND

1 — Defrost Board/Time Guard

II Control

2 — Fuse
3 — Fan No. 1
4 — Signal-LOC™ Device
5 — Outdoor-Fan Relay
6 — Outdoor-Fan Contactor
7 — Compressor Contactor
8 — Fan Motor Capacitors
9 — Circuit Breaker

10 — Fan No. 2

11 — Power Terminal Block
12 — Control Terminal Block
13 — Compressor Lockout (CLO2 for

Crankcase Heater)

14 — Control Relay (CR3)
15 — Liquid Line Solenoid
16 — Control Relay (CR2)
17 — No Dump Relay (NDR)
18 — Oil Pressure Switch
19 — Fusible Plug (hidden)

20 — High-Pressure Switch
21 — Compressor
22 — Capacity Control Solenoid
23 — Filter Drier
24 — Muffler
25 — Oil Solenoid
26 — Reversing Valve
27 — Accumulator
28 — Coil

Fig. 2 — Component Locations

2

1

4

3

541A120, 180

38 1/4"

26 11/16"

Fig. 3 — Weight Distribution