12 typical wiring schematics (cont) – Bryant CeilingPAC 502A User Manual

Page 12

Advertising
background image

12

TYPICAL WIRING SCHEMATICS (cont)

LEGEND

AHA

—

Adjustable Heat Anticipator

C

—

Contactor Compressor

CAP

—

Capacitor

CB

—

Circuit Breaker

CC

—

Cooling Compensator

CDT

—

Compressor Discharge Thermostat

CH

—

Crankcase Heater

COMP

—

Compressor Motor

EQUIP

—

Equipment

GND

—

Ground

HPS

—

High-Pressure Switch

HR

—

Heater Relay

IFC

—

Indoor-Fan Contactor

IFM

—

Indoor-Fan Motor

IFR

—

Indoor-Fan Relay

JB

—

Junction Box

L

—

Light

LPS

—

Low-Pressure Switch

NEC

—

National Electrical Code

OFM

—

Outdoor-Fan Motor

PL

—

Plug Assembly

QT

—

Quadruple Terminal

RC

—

Run Capacitor

TB

—

Terminal Block

TC

—

Thermostat-Cooling

TH

—

Thermostat-Heating

TRAN

—

Transformer

Marked Wire

Denotes connection point between
subbase and thermostat

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Field Splice

Splice (Marked)

Factory Splice

Factory Wiring

Accessory or Optional Wiring

Field Control Wiring

Field Power Wiring

To indicate common potential
only, not to represent wiring

502A048,060, 230-1-60 Units

NOTES:
2. If any original wires furnished must be replaced, it should be

replaced with 90 C or its equivalent.

3. Numbers indicate the line location of used contacts. A bracket

over 2 numbers signifies a single-pole double-throw contact. An
underlined number signifies a normally closed contact. Plain (no
line) number signifies a normally open contact.

4. Must use thermostat HH07AT170, 172 or 174 with subbase

HN63AZ176, 177 or 179.

5. Neutral for 240/416 v supply (Canada only).
6. Separate field power supply required for electric heater

accessory.

7. The 10-kW, 15-kW and 20-kW heater assemblies for

502A048,060 are wired for 3 phase. See heater label diagram for
1-phase rewiring procedure.