SERVICE

CAUTION:

When servicing unit, shut off all electri-

cal power to unit to avoid shock hazard or injury from
rotating parts.

I. CLEANING

Inspect unit interior at the beginning of each cooling season
and as operating conditions require.

A. Outdoor Coil

Inspect coil monthly. Clean outdoor coil annually and as re-
quired by location or outdoor-air conditions.

Clean coil as follows:

1. Turn off unit power.

2. Remove and save top panel screws on outdoor unit.

3. Remove outdoor coil corner post. See Fig. 14. To hold

top panel open, place coil corner post between top panel
and side panel. See Fig. 15.

4. Remove bracket holding coil sections together at return

end of outdoor coil. Carefully separate the outer coil sec-
tion 3 to 4 in. from the inner coil section. See Fig. 16.

5. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and de-
bris. Clean the outer surfaces with a stiff brush in the
normal manner.

6. Reposition the outer coil section and secure the sections

together. Remove the coil corner post from between the
top panel and side panel. Install the coil corner post and
replace all screws removed in Step 2.

Fig. 13 — Heating Mode Operation

Fig. 14 — Cleaning Outdoor Coil

Fig. 15 — Propping Up Top Panel

—11—