Table 1 — Physical Data

UNIT 575A

090

OPERATING WEIGHT (lb)

Aluminum Coils (Standard)

540

Copper Coils (Optional)

608

RIGGING WEIGHT (lb)

Aluminum Coils (Standard)

590

Copper Coils (Optional)

658

REFRIGERANT*

R-22

COMPRESSOR

Reciprocating, Semi-Hermetic

Quantity...Type

1...06DA818

Quantity Cylinders

4

Speed (rpm)

1750

Oil Charge (oz) (ea)

88

OUTDOOR FAN

Propeller; Direct Drive

Quantity...rpm

1...1100

Diameter (in.)

26

Motor Hp (NEMA)

3

4

Nominal Airflow (cfm)

6500

OUTDOOR COIL

Enhanced Copper Tubes,

Aluminum Lanced Fins

Face Area (sq ft)

18.0

Storage Capacity (lb)†

16.56

Fins/in.

17.0

Rows (No.)

2

CONNECTIONS (Sweat)

Suction (in.)

1

1

8

Liquid (in.)

1

2

CONTROLS

Pressurestat Settings (psig)

High Cutout

426

Ϯ

7

Cut-in

320

Ϯ

20

Low Cutout

7

Ϯ

3

Cut-in

22

Ϯ

5

Defrost Thermostat

Initiate Defrost (F)

28

Terminates Defrost (F)

65

LEGEND

NEMA — National Electrical Manufacturing Association

*Unit is factory supplied with holding charge only.

†Storage capacity of coil with coil 80% full of liquid R-22 at 120 F.

II. RIG AND MOUNT THE UNIT

CAUTION:

Be sure unit panels are securely in place

prior to rigging.

A. Rigging

The unit is designed for overhead rigging. Refer to rigging
label for preferred rigging method. Spreader bars are not re-
quired if top crating is left on unit. All panels must be in place
when rigging. (See Fig. 3.) As further protection for coil faces,
plywood sheets may be placed against sides of unit, behind
cables. Run cables to a central suspension point so that angle
from the horizontal plane is not less than 45 degrees. Raise
and set unit down carefully.

If it is necessary to roll unit into position, mount unit on rails,
using a minimum of 3 rollers. Apply force to rails, not unit. If
unit is to be skidded into position, place it on a large pad and
drag it by the pad. Do not apply any force to unit.

Raise from above to lift unit from rails or pad when unit is in
final position.

After unit is in position, remove all shipping wrapping and
top crating.

B. Mounting

The unit must be elevated to ensure drainage from basepan
during sub-freezing conditions and to prevent or limit block-
age of outdoor coil during snowfall. Consideration should be
given to specific geographical areas when determining height
of unit elevation.

C. Compressor Mounting

As shipped, compressors are held down by 4 bolts. After unit
is installed, loosen each bolt until the snubber washer can be
moved with finger pressure. See Fig. 4.

UNIT

MAX WEIGHT

A

B

C

w/Al

Coil

w/Cu

Coil

Lb

Kg

Lb

Kg

in.

mm

in.

mm

in.

mm

575A090

590

268

658

298

45.0

1143

38.5

989

43.5

1105

Al

Aluminum-Fin

Cu — Copper-Fin

Fig. 3 — Rigging Label

Fig. 4 — Compressor Mounting

—3—