Table 4 — Electrical Data

UNIT
575A

NOMINAL VOLTAGE

(V-Ph-Hz)

VOLTAGE RANGE

COMPRESSOR

OFM

POWER SUPPLY

MINIMUM DISCONNECT

Min

Max

RLA

LRA

FLA

MCA

MAX FUSE OR

HACR BRKR AMPS

FLA

LRA

090

208/230-3-60

187

254

31.5

160

3.1

42.5

50

45

177

460-3-60

414

508

15.7

80

1.4

21.0

25

25

89

LEGEND

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

NEC

National Electrical Code

OFM

Outdoor Fan Motor

RLA

Rated Load Amps

NOTES:
1. In compliance with NEC requirements for multimotor and combina-

tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
voltage imbalance.

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=

457

(AB) 457

Ϫ

452 = 5 v

(BC) 464

Ϫ

457 = 7 v

(AC) 457

Ϫ

455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance

7

% Voltage Imbalance = 100

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

Table 5 — Accessory Electric Heater Data

UNIT

524A-H

NOMINAL kW

V-PH-HZ

HEATER

PART NO.

HEATER

AMPS

MCA*

MOCP*

090

5

240-3-60

CAELHEAT001A00

12.0

25.6

30

480-3-60

CAELHEAT002A00

6.0

12.3

15

10

240-3-60

CAELHEAT004A00

24.1

40.7

50

480-3-60

CAELHEAT005A00

12.0

19.8

25

15

240-3-60

CAELHEAT007A00

36.0

55.7

80

480-3-60

CAELHEAT008A00

18.0

27.4

40

25

240-3-60

CAELHEAT010A00

60.1

85.8

125

480-3-60

CAELHEAT011A00

30.1

42.4

60

35

240-3-60

CAELHEAT013A00

84.0

115.8

175

480-3-60

CAELHEAT014A00

42.1

57.4

80

LEGEND

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat accessory

and air handler.

NOTES:
1. MCA and MOCP values apply to both standard and alternate factory-

supplied motors.

2. Electrical resistance heaters are rated at 240 v or 480 v. To deter-

mine heater capacity (kW) at unit nameplate voltage, multiply 240-v
or 480-v capacity by multipliers found in table below.

HEATER RATING

VOLTAGE

ACTUAL SITE VOLTAGE

200

208

230

240

400

440

460

480

240

.694

.751

.918

1

480

.694

.840

.918

1

NOTE: The following equation converts kW of heat energy to Btuh:
kW x 3,412 = Btuh.

—7—