Bryant Air Handling Units 524J User Manual

Page 10

Advertising
background image

10

Unit Positioning —

The unit can be mounted on the

floor for vertical application with return air entering the face of

the unit and supply air discharging vertically through the top of

the unit. The unit can also be applied in a horizontal

arrangement with return air entering horizontally and the

supply air discharging horizontally. When applying the unit in

a horizontal arrangement, ensure the condensate drain pan is

located at the bottom center of the unit for adequate condensate

disposal. See Fig. 5 for condensate connections for each unit

position.
Typical positioning and alternate return air locations are shown

in Fig. 5. Alternate return air locations can be used by moving

the unit panel from the alternate return air location to the

standard return air location. Refer to overhead suspension

accessory drawing (Fig. 6) for preferred suspension technique.

The unit needs support underneath to prevent sagging.

Fig. 5 — Typical Unit Positioning

Fig. 6 — Preferred Suspension Technique

IMPORTANT: Do NOT attempt to install unit with return

air entering top panel of unit. Condensate will not drain

from unit.

LEGEND

Accessory Line

Alternate Air Intake and Discharge

Air Intake and Discharge

Note: Maintain recommended clearances

per Figs. 1A–1B

UNIT SIZES 14 - 16

NOTE: Dimensions in [ ] are millimeters

UNIT SIZES 07 - 12

OVERHEAD SUSPENSION ACCESSORY