Bryant Air Handling Units 524J User Manual

Page 18

Advertising
background image

18

Legend and Notes For Tables 4 and 5

Fig. 16 — Unit Wiring

LEGEND

*Motors are designed for satisfactory operation within 10% of nominal volt-

ages shown. Voltages should not exceed the limits shown in the Voltage Lim-
its column.

NOTES:
1. Minimum circuit amps (MCA) and MOCP values are calculated in accor-

dance with NEC (National Electrical Code), Article 440.

2. Motor FLA values are established in accordance with UL (Underwriters’

Laboratories) Standard 1995.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percentage of
voltage imbalance.

EXAMPLE: Supply voltage is 400-3-50.

AB = 393 v
BC = 403 v
AC = 396 v

Determine maximum deviation from average voltage

(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v

Maximum deviation is 6 v.
Determine percent voltage imbalance.

This amount of phase imbalance is satisfactory because it is below the maxi-
mum allowable 2%.

FLA

Full Load Amps

MOCP

Maximum Overcurrent Protection

% Voltage Imbalance = 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

393 + 403 + 396

3

=

1192

3

= 397

% Voltage Imbalance = 100 x

6

397

= 1.5%

IMPORTANT:

If the supply voltage phase imbalance is more than

2%, contact your local electric utility company immediately.

LEGEND

NOTE: Use copper conductors only.

EQUIP

Equipment

GND

Ground

HC

Heating Contactor

HTR

Electric Heater

IFC

Indoor-Fan Contactor

IFM

Indoor-Fan Motor

TB

Terminal Block

T’STAT

Thermostat

Factory Wiring

Field Control Wiring

Advertising