9

1030H Start pattern number

0 ~ 7

1040H~

1047H

Actual step number setting inside the
correspond pattern

0 ~ 7 = N, indicate that this pattern is executed from step 0 to step N

1050H~

1057H

Cycle number for repeating the
execution of the correspond pattern

0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times

1060H~

1067H

Link pattern number setting of the
correspond pattern

0 ~ 8, 8 indicates the program end. 0~7 indicates the next execution pattern number after executing
the current pattern

2000H~

203FH

Pattern 0~7 temperature set point
setting; Pattern 0 temperature is set to
2000H~2007H

-999 ~ 9999

2080H~

20BFH

Pattern 0~7 execution time setting
Pattern 0 time is set to 2080H~2087H

Time 0 ~ 900 (1 minute per scale)

6.

Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data = FF00H for bit set, 0000H for bit clear)

0810H Communication write-in selection

Communication write in disabled: 0 (default), Communication write in enabled: 1

0811H Temperature unit display selection

o

C / linear input (default) : 1 ,

o

F : 0

0812H Decimal point position selection

Except for the thermocouple B, S, R type, all the other thermocouple type are valid. (0 or 1)

0813H AT setting

OFF: 0 (default), ON : 1

0814H Control RUN/STOP setting

0: STOP, 1 : RUN (default)

0815H

STOP setting for PID program
control

0: RUN (default), 1: STOP

0816H

Temporarily STOP for PID program
control

0: RUN (default), 1: Temporarily STOP

0817H Valve feedback setting status

0: w/o feedback (default), 1: feedback function

0818H Auto-tuning valve feedback status

0: Stop AT (default), 1: Start AT

7.

Communication Transmission Format : Command Code: 02: read N bits, 05: write 1 bits, 03: read N words, 06: write 1 words