2 4 specifications, Temperature sensor type and temperature range – B&B Electronics DELTA Temperature Controller DTB Series User Manual

Page 3

Advertising
background image

2

4

Specifications

5

Temperature Sensor Type and Temperature Range

Input Temperature Sensor Type

Register Value

LED Display

Temperature Range

0~50mV Analog Input

17

-999 ~ 9999

4~20mA Analog Input

16

-999 ~ 9999

0~20mA Analog Input

15

-999 ~ 9999

0V~10V Analog Input

14

-999 ~ 9999

0V~5V Analog Input

13

-999 ~ 9999

Platinum Resistance (Pt100)

12

-200 ~ 600

o

C

Platinum Resistance (JPt100)

11

-20 ~ 400

o

C

Thermocouple TXK type

10

-200 ~ 800

o

C

Thermocouple U type

9

-200 ~ 500

o

C

Thermocouple L type

8

-200 ~ 850

o

C

Thermocouple B type

7

100 ~ 1800

o

C

Thermocouple S type

6

0 ~ 1700

o

C

Thermocouple R type

5

0 ~ 1700

o

C

Thermocouple N type

4

-200 ~ 1300

o

C

Thermocouple E type

3

0 ~ 600

o

C

Thermocouple T type

2

-200 ~ 400

o

C

Thermocouple J type

1

-100 ~ 1200

o

C

Thermocouple K type

0

-200 ~ 1300

o

C

Note 1 : An external 250

Ω precision resistor should be connected when the current input is selected as the input temperature sensor type..

Note 2 :

(Operation mode) must be set if user wish to specify decimal point position. Except for the thermocouple B, S, R type, the decimal

point positions of all the other thermocouple type input sensors can be set.

The default range of analog input is -999 ~ 9999. For example, when a 0~20mA analog input is selected as the input temperature sensor type, -999

indicates 0mA and 9999 indicates 20mA. If change the input range to 0 ~ 2000, then 0 indicates 0mA and 2000 indicates 20mA. One display scale is
equal to 0.01mA.











Input Voltage

100 to 240VAC 50/60Hz

Operation Voltage Range

85% to 110% of rated voltage

Power Consumption

5VA max.

Memory Protection

EEPROM 4K bit (non-volatile memory (number of writes: 100,000)

Display Method

2 line x 4 character 7-segment LED display Process value(PV): Red color, Set point(SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
3-wire Platinum RTD: Pt100, JPt100

Sensor Type

Analog input: 0~5V, 0~10V, 0~ 20 m A, 4~20 m A, 0~50mV

Control Mode

PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load
Voltage pulse output: DC 14V, Max. output current 40mA
Current output: DC 4 ~ 20m A output (Load resistance: Max. 600

Ω)

Control Output

Linear voltage output: 0~5V, 0~10V

Display Accuracy

0 or 1 digit to the right of the decimal point (selectable)

Sampling Rate

Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan

RS-485 Communication

MODBUS ASCII / RTU communication protocol

Vibration Resistance

10 to 55Hz, 10m/s

2

for 10min, each in X, Y and Z directions

Shock Resistance

Max. 300m/ s

2

, 3 times in each 3 axes, 6 directions

Ambient Temperature

0

o

C to +50

o

C

Storage Temperature

-20

o

C to +65

o

C

Altitude

2000m or less

Relative Humidity

35% to 80% (non-condensing)

Advertising
This manual is related to the following products: