B&B Electronics DELTA Temperature Controller DTB Series User Manual

Page 6

Advertising
background image

5

7

Dual Loop Output Control (Heating / Cooling Control)

OFF

PV

Set point

ON

Heating

Dead band

Heating hysteresis

Figure 1. Output

during dual loop output control

operation of ON/OFF control

Cooling hysteresis

Cooling

PV

0

Output

Dead band: dead
band width=positive

Set point

Heating

Cooling

Figure 2. PID

Dead Band is positive

control,


Temperature control can be achieved either by heating or cooling. In DTB series, heating and
cooling can be operated simultaneously (Dual Loop output control) to perform temperature
control. When Dual Loop output control are used, two control outputs must be connected to the
heating and cooling devices. Please refer to the following for the operation:

: This parameter is used to select heating or cooling action if operate either heating or

cooling function in this controller. When selecting

, 1st output group is heating (reverse)

control, and when selecting

, 1st output group is cooling (forward) control. At this

moment, 2nd output group is regarded as an alarm output. If user select

or

, it

indicates that user can operate Dual Loop output control function in this controller. When
selecting

, 1st output group is heating (reverse) control and 2nd output group is cooling

(forward) control. When selecting

, 1st output group is cooling (forward) control and 2nd

output group is heating (reverse) control.
In DTB series, P (Proportional Band), I(Integral Time) and D(Derivative Time) parameters are
automatically set by using the Auto-tuning (AT) function.

: This parameter is for the control mode that must be Dual Loop output control with PID

control method configured. The value of P, I and D of 1st output group can be set immediately.
The P value of 2nd output group is equal to (P value of 1st output group) x

and the

value of I and D of 2nd output group are the same as the value of I and D of 1st output group.

: Dead Band, shown as the following figure 1, 2 and 3. This parameter sets an area in

which the heating and cooling control output is 0 centering around the set point in a Dual Loop
output control mode.

:

Settings lock. To avoid incorrect operation, two key lock functions are provided.

: Lock 1 can lock all settings. All parameters and temperature settings can be locked to

disable changes.

: Lock 2 can lock settings except the SV (Set point) value. All

parameters and temperature settings can be locked with the exception of the SV value. Press

and

key simultaneously, the “Lock” status can be released.









































PV

0

Output

Dead band: dead
band width=negative

Set point

Heating

Cooling

Figure 3. PID

Dead Band is negative

control,