Burnham SM-6 User Manual
Page 24
 
24
where conditions warrant) to fl ush out the sediment 
chamber so the device will be free to function properly.
Low water fuel cutoffs and water feeders should be
dismantled annually by qualifi ed personnel, to the 
extent necessary to insure freedom from obstructions 
and proper functioning of the working parts. Inspect 
connecting lines to boiler for accumulation of mud, 
scale, etc. and clean as required. Examine all visible 
wiring for brittle or worn insulation and make sure 
electrical contacts are clean and that they function 
properly. Give special attention to solder joints on 
bellows and fl oat when this type of control is used. 
Check fl oat for evidence of collapse and check mercury 
bulb (where applicable) for mercury separation or 
discoloration. Probe type low water cutoff should be 
removed once a year, examined and cleaned of any 
dirt accumulations to assure proper operation. Do not 
attempt to repair mechanisms in the fi eld. Complete 
replacement mechanisms including necessary gaskets 
and installation instructions are available from the 
manufacturer.
9
LUBRICATION
There are no parts requiring lubrication on the part of 
the serviceman or the homeowner. Circulator bearings 
are water lubricated. Fan motor bearings are factory 
sealed.
Figure 16
CLEANING OF VENT SYSTEM, BOILER FLUES, AND BURNERS