Chiller – Bacharach AGM300 User Manual

Page 8

Advertising
background image

vi

Instruction 3015-4275

AGM300 / ADM800 Refrigerant Gas Leak Monitor Mechanical Room Placement


















The ADM800 should be mounted outside of the mechanical room or at least just inside of a door to the room.
This is the “split architecture design” for safety of the operator. The ADM800 can be located up to 4500 feet
from the AGM300. The ADM800 is the main interface by which you program the AGM300, acknowledge
alarms, and observe conditions inside of the mechanical room. Note that there are two additional alarm relay
contacts in the ADM800 that can be programmed to alarm with “leak, spill, evacuate, fault or monitor on”.


AGM300
Ammonia
Gas
Monitor

Outside Hallway

Machine Room

Sample Inlet Pickup Points

Chiller

Sample Inlet
Pickup Point

Aux. Horn/Strobe
Remote Alarm

Fresh air purge
from area away
from ammonia
gas

Exhaust Fan

ADM800
Ammonia Display
Module outside of
mechanical room