Dimensions, Dimensions (in.) sound power (dba) – Bryant TWO-SPEED PURON PLUS ELECTRIC HEAT PUMP 698B User Manual

Page 2

Advertising
background image

—2—

DIMENSIONS

A01063

DIMENSIONS (IN.)

SOUND POWER (dBA)

*Sound levels are equivalent at high and low speeds.

UNIT

SIZE

SERIES

A

B

C

D

E

F

G

H

K

L

M

N

MINIMUM MOUNTING

PAD DIMENSIONS

024

A

33-13/16 22-1/2

26-3/16

4-1/8

7-1/8

21-15/16 28-3/8

5/8

12

13-3/4

12

2-3/8

20 x 27

036

A

27-13/16

30

33

5-1/16

9-11/16 15-15/16 22-3/8

3/4

16-1/4

14

13-1/8

2-15/16

26 x 32

048

A

39-13/16

30

33

5-1/16

9-11/16 27-15/16 34-3/8

7/8

16-1/4

14-1/4

14-1/2

2-15/16

26 x 32

060

A

39-13/16

30

33

5-1/16

9-11/16 27-15/16 34-3/8

7/8

16

13-3/4

15-3/4

2-15/16

26 x 32

UNIT

SIZE

SOUND
LEVEL*

OCTAVE BAND CENTER FREQUENCY (Hz)

125

250

500

1000

2,000

4,000

8,000

High Speed

024

74

52.9

58.4

58.8

68.5

57.7

53.0

45.4

036

74

53.9

59.4

60.8

65.5

58.7

53.5

48.4

048

75

53.9

59.9

59.8

63.0

60.7

53.5

48.9

060

76

52.4

58.4

58.8

62.0

63.2

58.0

52.4

AIR DISCHARGE

AIR DISCHARGE

AIR IN

AIR IN

AIR IN

3

/

8

"

DIA. TIEDOWN KNOCKOUTS

(2) PLACES

L

K

N

E

D

C

L

ACCESS

PANEL

1

1

/

4

"

2

1

/

2

"

AIR DISCHARGE

1

3

/

4

"

4

3

/

16

"

3/8" DIA. LIQUID
LINE CONN.

H

DIA. VAPOR

LINE CONN.

7/8" DIA. HOLE

FIELD POWER SUPPLY CONN.

7

/

8

"

DIA.

HOLE WITH 1

1

/

8

"

DIA. KNOCKOUT

AND 1

3

/

8

"

DIA. KNOCKOUT

10

1

/

2

"

FIELD CONTROL
SUPPLY CONN

1

9

/

16

"

C

F

8

3

/

16

"

G

A

B

M

NOTES:

1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE
SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS 55

°

F,

(UNLESS LOW AMBIENT CONTROL IS USED) MAX. 125

°

F.

3. MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE IS 66

°

F.

4. SERIES DESIGNATION IS THE 14TH POSITION OF THE UNIT MODEL NUMBER.
5. CENTER OF GRAVITY .

Advertising