Specifications – Bryant TWO-SPEED PURON PLUS ELECTRIC HEAT PUMP 698B User Manual

Page 4

Advertising
background image

—4—

SPECIFICATIONS

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70). The ampacity of nonmetallic-sheathed cable (NM),

trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C
(140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the
NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

** Time-delay fuse or circuit breaker.

NOTES:

1. Copper wire must be used from service disconnect to unit.
2. All motors and compressors contain internal overload protection.
3. This product may not be used in low-ambient applications below 55°F outdoor ambient.

UNIT SIZE-SERIES

024-A

036-A

048-A

060-A

OPERATING WEIGHT (Lb)

188

243

282

327

ELECTRICAL

Unit Volts—Hertz—Phase

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

Operating Voltage Range*

187-253

187-253

187-253

187-253

Compressor— Rated Load Amps

10.6

14.1

22.3

28.3

Locked Rotor Amps

64.0

66.0

96.0

130.0

Condenser Fan Motor—Full Load Amps

0.5

0.84

1.1

1.1

Min Unit Ampacity for Wire Sizing

13.8

18.5

29.0

36.5

Min Wire Size (60°C Copper) AWG†

14

14

10

8

Min Wire Size (70°C Copper) AWG†

14

14

10

8

Max Wire Length (60°C) (Ft)‡

57

43

69

91

Max Wire Length (70°C) (Ft)‡

55

41

66

56

Max Branch Circuit Fuse Size**

20

30

45

60

COMPRESSOR AND REFRIGERANT

Compressor—

Manufacturer

Bristol

Type

Reciprocating

Temperature and Current Protection

Internal Overload

Refrigerant—

Type

Puron® (R-410A)

Amount (Lb)

6.1

10.0

13.9

15.3

Metering Device

Puron TXV Balance Port Hard Shutoff

CONDENSER COIL AND FAN

Coil—Face Area (Sq Ft)

10.8

12.12

18.2

18.2

Fins per In.—Rows—Circuits

25-1-2

20-2-3

20-2-5

20-2-5

Fan Motor—HP and RPM (PSC Type)

1/15 and 825

1/8 and 825

1/5 and 825

1/5 and 825

Volts—Hertz—Phase

208/230-60-1

Condenser Airflow (CFM)

1500

2500

3000

3100

OPTIONAL EQUIPMENT

Support Feet

KSASF0101AAA

Coastal Filter

KAACF0801MED

Snow Stand

KHASS0106MPK

KHASS0206MPK

Thermostat, Auto Changeover,

Non-Programmable, °F/°C, 2-stage heat/
2-stage cool in AC mode, 3-stage heat/
2-stage cool in HP mode

TSTATBBN2S01-B

Thermostat, Auto Changeover,

7-Day Programmable, °F/°C, 2-stage heat/
2-stage cool in AC mode, 3-stage heat/
2-stage cool in HP mode

TSTATBBP2S01-B

Thermidistat Control, Programmable/Non-

Programmable Thermostat with Humidity Control

TSTATBBPRH01-B

Outdoor Air Temperature Sensor

TSTATXXSEN01-B

Backplate for Non-Programmable Thermostat

TSTATXXNBP01

Backplate for Programmable Thermostat

TSTATXXPBP01

Thermostat Conversion Kit (4 to 5 wire)—10 Pack