Sec IV- 2

Troubleshooting

CONDITION

POSSIBLE CAUSE

SUGGESTED CORRECTION

Suction lift too high

Do not attempt lifts exceeding
22 feet.

Restricted suction strainer

Remove obstruction from
suction hose strainer.

Clean and tighten all suction
connections. Check suction
hose and hose gaskets for
possible defects.

Primer not operated long
enough.

Proper priming procedures
should be followed. Do not
release the primer control
before assuring a complete
prime.

Suction Connections

PUMP LOSES PRIME OR
WILL NOT PRIME (cont'd.)

Air Leaks

Attempt to locate and correct
air leaks using the following
procedure:

1. Perform dry vacuum test on
pump per NFPA standards with
22 inches minimum vacuum
required with loss not to
exceed 10 inches of vacuum in
5 minutes.

2. If a minimum of 22 inches of
vacuum cannot be achieved,
the priming device or system
may be defective, or the leak is
too big for the primer to
overcome (such as an open
valve).

NOTICE: Do not run the primer over 45 seconds. If prime is not achieved in 45 seconds, stop and
look for causes (air leaks or blocked suction hose).