Hale products inc, Impeller maintenance recommended clearances – Hale PSD User Manual

Page 20

Advertising
background image

Hale Products Inc.

Impeller Maintenance Recommended Clearances

This table lists recommended clearances for I.R.P.S. fire pumps (750 gpm to 1500 gpm). Be

sure to check your impeller for damage before proceeding to undersize wear rings. When

turning impellers to fit undersize rings, caution must be exercised that the seal ring surface

runs true with the bore within .002.

1/32

1/16

Standard

Undersize

Undersize

750/1250 gpm

A

6.067

6.036

6.005

6.069

6.037

6.006

B

6.051

6.020

5.989

6.050

6.019

5.988

C

6.051

6.020

5.989

6.050

6.019

5.988

D

6.067

6.036

6.005

6.069

6.037

6.006

1500 gpm

A

6.517

6.486

6.455

6.519

6.488

6.457

B

6.501

6.470

6.439

6.500

6.469

6.438

C

6.501

6.470

6.439

6.500

6.469

6.438

D

6.517

6.486

6.455

6.519

6.488

6.457

Advertising