Always remove the negative terminal

first.

3. Check the specific gravity of each

cell with a hydrometer. All cells

should have a specific gravity of

1.250 with no more than 0.50

variation between any two cells. If

the specific gravity is less than 1.225

or varies by more than 0.50 between

any two cells replace the battery.

4. Connect battery load test

instrument to the terminals and place

battery under simulated starting load

with the test instrument. The meter

should read 9 volts or more when the

simulated starting load is applied. If

the meter does not read 9 volts,

replace the battery.

NOTE: Dispose of used battery
in accordance with local
ordinances.

5. Reconnect the cables to the

positive and negative terminals.

Always connect the negative

terminal last.

6. Replace pump covers as

necessary.

7. Return pump to storage area for

operation.

PORTABLE PUMP BATTERY

POS BATTERY

TERMINAL

NEG BATTERY

TERMINAL

CELL CAPS